Plan Review Notes
Plan Review Notes For Permit 04090032
Permit Number 04090032
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-09-28 00:00:001) ELECTRONIC SWITCHES, CHAIN AND
 LOCK REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 2) ONLY ONE FIRE HYDRANT IS SHOWN. ON
 PAGE C-1 AN EXISTING FIRE HYDRANT IS
 SHOWN, BUT A PRIVATE FIRE HYDRANT
 WILL BE NEEDED WITHIN THE SITE. THE
 FIRE DEPARTMENT SPRINKLER CONNECTIONS
 MUST BE WITHIN 150 FEET OF A FIRE
 HYDRANT.
  
 3) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. A MINIMUM OF 6"
 HIGH NUMBERS.
  
 4) NO FIRE SPRINKLER PLANS OR HYDRAULIC
 CALCUALTIONS PROVIDED WITH PLANS.
 FS 553.895 (2) REQUIRES FIRE SPRINKLER
 PROTECTION IN ALL THREE STORIES
 BUILDINGS.
  
 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 6) ALL NEW STAIRS AND RAMPS SHALL BE
 PROVIDED WITH HANDRAILS.
  
 7) NO MENTION OF ANY FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910