| 2004-09-28 00:00:00 | 1) ELECTRONIC SWITCHES, CHAIN AND | | | LOCK REQUIRED ON FIRE LINE BACKFLOW | | | DEVICE. | | | | | | 2) ONLY ONE FIRE HYDRANT IS SHOWN. ON | | | PAGE C-1 AN EXISTING FIRE HYDRANT IS | | | SHOWN, BUT A PRIVATE FIRE HYDRANT | | | WILL BE NEEDED WITHIN THE SITE. THE | | | FIRE DEPARTMENT SPRINKLER CONNECTIONS | | | MUST BE WITHIN 150 FEET OF A FIRE | | | HYDRANT. | | | | | | 3) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. A MINIMUM OF 6" | | | HIGH NUMBERS. | | | | | | 4) NO FIRE SPRINKLER PLANS OR HYDRAULIC | | | CALCUALTIONS PROVIDED WITH PLANS. | | | FS 553.895 (2) REQUIRES FIRE SPRINKLER | | | PROTECTION IN ALL THREE STORIES | | | BUILDINGS. | | | | | | 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR HANDRAILS AND | | | GUARDRAILS. | | | | | | 6) ALL NEW STAIRS AND RAMPS SHALL BE | | | PROVIDED WITH HANDRAILS. | | | | | | 7) NO MENTION OF ANY FIRE EXTINGUISHERS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|