| Date |
Text |
| 2004-09-21 00:00:00 | ******** UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE RISER DIAGRAM DOES |
| | NOT SEEM TO INDICATE ANY MAINS?? 225.31, |
| | 230.70 ETC. |
| | GROUPING OF MAINS? 230.72 |
| | |
| | 2)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS FROM "MAINS" TO |
| | PANELS. REQUIRED AFTER THE FIRST MEANS |
| | OF DISCONNECT. 250.24 |
| | |
| | 3)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 4) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 5)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 210.12 2002 NEC. |
| | PLEASE ALSO SEE SD'S ARE INDICATED AS |
| | BEING ON THE KITCHEN LT CIRCUIT? |
| | WILL THIS ALSO BE ARC FAULT PROTECTED? |
| | PLEASE SEE NOTE #30 ON GENERAL NOTES. |
| | SD'S REQUIRED TO BE ARC FAULT ALSO, SEE |
| | ABOVE. |
| | |
| | 6)NOTE: PLEASE SEE DISCONNECTING CLEAR- |
| | -ENCE FOR A/C UNIT. 110.26 |
| | |
| | 7)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | FOR SERVICE. |
| | |
| | 8)NOTE: PLEASE SEE FAC 61G1-16.004 AND |
| | FS 481.219 FOR MISSING REQUIRED INFOR- |
| | -MATION ON TITLE BLOCK FOR ARCHITECT |
| | FIRM. THIS IS REQUIRED ON ALL SHEETS |
| | WHEATHER OR NOT COMMENT IS MADE BY |
| | OTHER REVIEWERS. |
| | PLEASE ALSO SEE PLANS ARE REQUIRED TO |
| | HAVE AN ORIGINAL SIGNATURE AND TO BE |
| | SEALED. 481.221. |
| | |
| | 9)NOTE: PLEASE VERIFY HOW MANY UNITS |
| | THERE ARE GOING TO BE? ATTACHED? |
| | SEPARATE SERVICES DETACHED BLDGS? |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |