| 2005-05-18 00:00:00 | ************ UNSAT ************ |
| | |
| | **PLEASE SEE PLANS AND RISER DIAGRAM |
| | HAVE COMPLETELY CHANGED FROM ORIG PLANS. |
| | |
| | 1)NOTE: PLEASE SEE NEW RISER NOW |
| | INDICATES THREE ELECTRICAL PANELS, |
| | HOWEVER NO OCP IS SHOWN ON RISER FOR NEW |
| | PANELS. |
| | IS THERE NOW A PANEL SCHEDULE FOR NEW |
| | METER/MAIN COMBO. |
| | 215.5,240.4, 310.16 ETC. |
| | |
| | 2)NOTE: PLEASE SEE ONLY ONE PANEL IS |
| | SHOWN ON ELECTRICAL PLANS AND RISER |
| | SHOWS 3. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE NUMEROUS ITEMS ON |
| | PANEL SCHEDULE INDICATE 20A OCP ON #14 |
| | AWG. PLEASE SEE 310.16,240.4. |
| | |
| | 4)NOTE: |
| | |
| | 5)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL |
| | TUB IS NOW ADDED TO PANEL SCHEDULE, |
| | HOWEVER NO ELECTRICAL IS SHOWN ON PLANS. |
| | PLEASE ALSO SEE 680.71 FOR REQUIRED |
| | INDICATION OF GFI PROTECTION. |
| | |
| | 6)NOTE: PLEASE CORRELATE THE NUMBER OF |
| | RECESSED LTS ON PLANS WITH THE # OF |
| | RECESSED LTS INDICATED ON PANEL |
| | SCHEDULE/LOAD CALCULATIONS. |
| | PLEASE SEE SOME MODELS SHOW THESE AS |
| | "OPT". EACH PLAN MUST REFLECT THE ACTUAL |
| | INSTALLATION PER WHICH ARE INSTALLED OR |
| | NOT INSTALLED. |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPT |
| | REQUIRED IN BATHRM 210.52D. |
| | |
| | 8)NOTE: PLEASE SEE MISSING GFI ALONG |
| | KITCHEN COUNTERSPACE. |
| | |
| | PLEASE SEE MANY OF THESE ITEMS HAVE BEEN |
| | REDLINED AT LOCATIONS ON PLANS AT |
| | LOCATIONS OF NOTES. |
| | |
| | *** PLEASE BE SURE ALL PLANS ARE SIGNED |
| | BY THE ARCHITECT OF RECORD. |
| | FS 481.025 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |