2004-11-12 00:00:00 
 ******** NOTE **********
  
 PLEASE SEE LOAD CALCS SHOWS HI-HAT LOAD
 AT 35.25 KW? 47@75W IS 3525W??
  
 PLEASE SEE BELOEW LOAD CALCS, SERVICE
 INDICATES 200A'S YET RISER SHOWS
 300A'S.
  
 PLEASE SEE SERVICE SIZE HAS NOW BEEN
 CHANGED TO A 300A SERVICE.
 A #2 FOR GROUNDING ELECTRODE
 CONDUCTOR.250.66
  
 SERVICE MAY GO BACK TO 200A'S ONCE LOAD
 CALCS ARE ADJUSTED DUE TO HI-HAT
 LOAD.??
  
 VERIFY OCP FOR AHU#2, 5KW W/ 50A OCP.
  
 THE ABOVE WAS REDLINED ON PLANS AND MAY
 BE REVISED AFTER PERMIT IS ISSUED.
  
  
 ** SENT TO PLUMB DUE TO NEW SHEETS IN
 SETS.***