| 2004-09-20 00:00:00 | **** UNSAT *** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 2 )NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | 3)NOTE: PLEASE VERIFY OCP SHOWN FOR | | | WHAT APPEARS TO BE A 5KW HEAT-STRIP IN | | | \AHU #2. SHOWS 2P60A W/#6? | | | 424.3B | | | | | | 4)NOTE: PLEASE SEE NOTE #14 MENTIONS | | | SD'S TO WIRED INTO BATH /KIT LTS CIRCUIT | | | , PLEASE SEE THESE CIRCUITS WOULD THEN | | | BE REQUIRED TO BE ARC FAULT PER 210.12 | | | 2002 NEC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|