Plan Review Notes
Plan Review Notes For Permit 04090021
Permit Number 04090021
Review Stop B
Sequence Number 1
Notes
Date Text
2004-10-21 00:00:00DENIED
  
 1) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED ON THE ZERO LOT LINE. PLEASE
 SPECIFY THIS ON FLOOR PLAN.
  
 2) FBC 11-4.23.2 REQUIRES AT LEAST ONE
 FULL BATH TO HAVE A DOOR WITH A 29"
 CLEAR OPENING.
  
 3) SPECIFY THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR THE SLIDING GLASS
 DOOR AT THE DEN, OUTSWING DOOR AT THE
 MASTER SUITE AND OVERHEAD GOLF CART DOOR
  
 4) DETAIL 2 ON A9 SPECIFIES SEMCO
 CONNECTORS. PLEASE UPDATE TO CONNECTORS
 WITH STATE PRODUCT APPROVAL.
  
 5) UPDATE THE REFERENCE TO ASCE 7-88 IN
 THE GLASS BLOCK DETAIL ON A9. THE
 CURRENT STANDARD IS ASCE 7-98.
  
 6) SUBMIT THE UL OR OTHER LISTING
 INFORMATION AND MANUFACTURER'S SPECS.
 FOR THE ONE HOUR FIRE RATED GLASS BLOCK.
  
 7) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE MOUNT, FASTENERS AND FASTENER
 SPACINGS THAT WILL BE USED.
  
 8)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 9) SHEET A7 SPECIFIES THAT ATTIC VENTS
 ARE NOT ALLOWED ON THE ZERO LOT SIDE.
 ATTIC VENTS ARE ALLOWED ON ZERO LOT SIDE
 IN THIS JURISDICTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714