| 2004-10-21 00:00:00 | DENIED |
| | |
| | 1) ONE HOUR FIRE RATED GLASS BLOCK IS |
| | REQUIRED ON THE ZERO LOT LINE. PLEASE |
| | SPECIFY THIS ON FLOOR PLAN. |
| | |
| | 2) FBC 11-4.23.2 REQUIRES AT LEAST ONE |
| | FULL BATH TO HAVE A DOOR WITH A 29" |
| | CLEAR OPENING. |
| | |
| | 3) SPECIFY THE POSITIVE AND NEGATIVE |
| | WINDLOAD PRESSURES FOR THE SLIDING GLASS |
| | DOOR AT THE DEN, OUTSWING DOOR AT THE |
| | MASTER SUITE AND OVERHEAD GOLF CART DOOR |
| | |
| | 4) DETAIL 2 ON A9 SPECIFIES SEMCO |
| | CONNECTORS. PLEASE UPDATE TO CONNECTORS |
| | WITH STATE PRODUCT APPROVAL. |
| | |
| | 5) UPDATE THE REFERENCE TO ASCE 7-88 IN |
| | THE GLASS BLOCK DETAIL ON A9. THE |
| | CURRENT STANDARD IS ASCE 7-98. |
| | |
| | 6) SUBMIT THE UL OR OTHER LISTING |
| | INFORMATION AND MANUFACTURER'S SPECS. |
| | FOR THE ONE HOUR FIRE RATED GLASS BLOCK. |
| | |
| | 7) SUBMIT A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. SPECIFY |
| | THE MOUNT, FASTENERS AND FASTENER |
| | SPACINGS THAT WILL BE USED. |
| | |
| | 8)FBC 1005.4.5 (GLITCH AMENDMENTS |
| | JULY 1, 2003) REQUIRES AT LEAST ONE |
| | MEANS OF ESCAPE FROM A DWELLING WHEN |
| | SHUTTERED FOR IMPACT PROTECTION. THE |
| | MEANS OF ESCAPE SHALL BE WITHIN THE |
| | FIRST FLOOR OF THE DWELLING AND CAN NOT |
| | BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| | PART OF THE DWELLING SHALL HAVE ACCESS |
| | TO IT WITHOUT HAVING TO PASS THROUGH A |
| | LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| | INDICATE HOW COMPLIANCE WILL BE |
| | ACHIEVED. |
| | |
| | 9) SHEET A7 SPECIFIES THAT ATTIC VENTS |
| | ARE NOT ALLOWED ON THE ZERO LOT SIDE. |
| | ATTIC VENTS ARE ALLOWED ON ZERO LOT SIDE |
| | IN THIS JURISDICTION. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |