Plan Review Notes
Plan Review Notes For Permit 04090020
Permit Number 04090020
Review Stop E
Sequence Number 1
Notes
Date Text
2004-09-20 00:00:00******* UNSAT ******
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SEE OCP SHOWN FOR WHAT
 APPEARS TO BE A 5KW HEAT-STRIP IN AHU
 #2. SHOWN AS 60A AND #6. PLEASE VERIFY.
 424.3B
  
 3)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS MAY BE REQUIRED
 FOR REFERENCE ONLY BY OTHER REVIEWERS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  