| 2004-10-21 00:00:00 | DENIED |
| | |
| | 1) ONE HOUR FIRE RATED GLASS BLOCK IS |
| | REQUIRED ON THE ZERO LOT LINE. PLEASE |
| | SPECIFY THIS ON THE FLOOR PLAN. |
| | |
| | 2) FBC 11-4,23,2 REQUIRES AT LEAST ONE |
| | FULL BATH TO HAVE A DOOR WITH A 29" |
| | CLEAR OPENING. |
| | |
| | 3) SPECIFY THE POSITIVE AND NEGATIVE |
| | WINDLOAD PRESSURES FOR 7'X5' FIXED |
| | WINDOW AT THE BREAKFAST NOOK AND THE |
| | FRENCH DOOR AT THE CABANA BATH. |
| | |
| | 4) DETAIL 2 ON A9 SPECIFIES SEMCO |
| | CONNECTORS. PLEASE CHANGE TO CONNECTORS |
| | WITH STATE PRODUCT APPROVAL. |
| | |
| | 5) UPDATE THE REFERENCE TO ASCE 7-88 IN |
| | THE GLASS BLOCK DETAIL ON A9. THE |
| | CORRECT REFERENCE IS ASCE 7-98. |
| | |
| | 6) SUBMIT THE UL LISTING AND MANUFACT- |
| | URER'S SPECS. FOR THE ONE HOUR FIRE |
| | RATED GLASS BLOCK. |
| | |
| | 7) SUBMIT THE UL OR OTHER LISTING AND |
| | SPECS. FOR THE PREFAB FIREPLACE AND THE |
| | GAS BBQ. |
| | |
| | 8) THE CASEMENT WINDOWS IN BEDROOM #2 |
| | MUST MEET EGRESS REQUIREMENTS OF FBC |
| | 1005.4. |
| | |
| | 9) THE FLOOR PLAN SPECIFIES (2) 3080 |
| | WOOD DOORS AT FRONT ENTRY, HOWEVER NO |
| | PRODUCT APPROVALS FOR WOOD DOORS WERE |
| | SUBMITTED. |
| | |
| | 10) SUBMIT A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. SPECIFY |
| | THE MOUNT, FASTENERS, AND FASTENER |
| | SPACINGS THAT WILL BE USED. |
| | |
| | 11) FBC 1005.4.5 (GLITCH AMENDMENTS |
| | JULY 1, 2003) REQUIRES AT LEAST ONE |
| | MEANS OF ESCAPE FROM A DWELLING WHEN |
| | SHUTTERED FOR IMPACT PROTECTION. THE |
| | MEANS OF ESCAPE SHALL BE WITHIN THE |
| | FIRST FLOOR OF THE DWELLING AND CAN NOT |
| | BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| | PART OF THE DWELLING SHALL HAVE ACCESS |
| | TO IT WITHOUT HAVING TO PASS THROUGH A |
| | LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| | INDICATE HOW COMPLIANCE WILL BE |
| | ACHIEVED. |
| | |
| | 12) SECTION 1 ON A7 SPECIFIES THAT NO |
| | SOFFIT VENTS ARE ALLOWED ON ZERO LOT |
| | SIDE. THIS JURISDICTION DOES ALLOW THESE |
| | ON THE ZERO LOT SIDE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |