| Plan Review Notes For Permit 04090017 |
| Permit Number |
04090017 |
|
| Review Stop |
E |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2005-08-29 00:00:00 | ******** PLANS REDLINED ***** | | | | | | | | | | | | 1) PLEASE SEE LOAD FOR AHU ON PANEL "B" | | | HAS BEEN DECREASED TO CORRELATE WITH KW | | | RATING INDICATED ON LOAD CALCULATIONS, | | | HOWEVER, PLEASE SEE PANEL SCHEDULE STILL | | | INDICATES "60A" OVERCURRENT PROTECTION | | | FOR A 5KW HEAT STRIP? THIS IS OVERSIZED. | | | | | | 2) PLEASE SEE GROUNDING ELECTRODE | | | CONDUCTOR HAS NOW BEEN CHANGED TO A #1 ? | | | | | | PLEASE SEE PREVIOUS COMMENT MENTIONED A | | | 1/0 MIN IS REQUIRED FOR 400A SERVICE. | | | 250.66,310.15B6 | | | A NOTE WAS ADDED TO FEEDERS, HOWEVER | | | RISER WAS NOT CORRECTED. | | | RISER WENT FROM THE PREVIOUS #2 TO #1. | | | | | | THE ABOVE HAS BEEN REDLINED ON PLANS. |
|