| Plan Review Notes For Permit 04090017 |
| Permit Number |
04090017 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2005-08-24 00:00:00 | ** UNSAT *** | | | | | | | | | PLEASE SEE COMMENTS FROM PREVIOUS | | | REVIEW. | | | | | | 1)NOTE: PLEASE SEE PANEL "B" SHOWS AN | | | AHU WITH A 10KW HEATM HOWEVER LOADS | | | CALCS INDICATE A 5KW UNIT?? | | | PLEASE CORRELATE. | | | 215.5,220 | | | | | | 2)NOTE: PLEASE SEE GROUNDING ELECTRODE | | | WAS NOTED AND CHANGED UNDER FEEDERS TO | | | SUB-PANELS, HOWEVER PLEASE SEE GROUNDING | | | ELECTRODE CONDUCTOR SHOWN ON RISER STILL | | | SHOWS A #2. PLEASE CORRECT TO 1/0 MIN. | | | 250.66,310.15B6 | | | | | | 3)NOTE: REDLINED 210.52C1 FOR KITCHEN | | | GFI? THIS IS A REDLINED ITEM, HOWEVER | | | PLANS ARE COMING BACK. PLEASE SEE THIS | | | WAS NOT NOTED ON PREVIOUS NOTES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|