Plan Review Notes
Plan Review Notes For Permit 04090017
Permit Number 04090017
Review Stop E
Sequence Number 6
Notes
Date Text
2005-08-24 00:00:00** UNSAT ***
  
  
 PLEASE SEE COMMENTS FROM PREVIOUS
 REVIEW.
  
 1)NOTE: PLEASE SEE PANEL "B" SHOWS AN
 AHU WITH A 10KW HEATM HOWEVER LOADS
 CALCS INDICATE A 5KW UNIT??
 PLEASE CORRELATE.
 215.5,220
  
 2)NOTE: PLEASE SEE GROUNDING ELECTRODE
 WAS NOTED AND CHANGED UNDER FEEDERS TO
 SUB-PANELS, HOWEVER PLEASE SEE GROUNDING
 ELECTRODE CONDUCTOR SHOWN ON RISER STILL
 SHOWS A #2. PLEASE CORRECT TO 1/0 MIN.
 250.66,310.15B6
  
 3)NOTE: REDLINED 210.52C1 FOR KITCHEN
 GFI? THIS IS A REDLINED ITEM, HOWEVER
 PLANS ARE COMING BACK. PLEASE SEE THIS
 WAS NOT NOTED ON PREVIOUS NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW