| Plan Review Notes For Permit 04090017 |
| Permit Number |
04090017 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-08-18 00:00:00 | ************ UNSAT ************* | | | | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM NOW | | | SHOWS OCP FOR EACH PANEL. PLEASE SEE | | | RISER NOW SHOWS PANEL "B" UPGRADED FROM | | | THE PREVIOUS 150A PANEL TO 200A BRKR | | | FEEDING A 200A PANEL. THIS IS OK, | | | HOWEVER PLEASE SEE FEEDERS WERE NOT | | | UPGRADED FROM 150A TO 200A. PLEASE SEE | | | 310.15B6 FOR MIN FEEDERS. | | | PLEASE SEE MIN CONDUIT SIZE PER TABLES | | | IN CHAPTER 9. | | | | | | 2)NOTE: PLEASE SEE NOW SERVICE IS BEING | | | SHOWN UPGRADED FROM PREVIOUS 300A'S TO | | | 400A'S. PLEASE SEE MIN GROUNDING | | | ELECTRODE CONDUCTOR IS TO BE A 1/0 PER | | | 310.15B6, 250.66. | | | | | | 3)NOTE: PLEASE SEE REVISED LOAD | | | CALCULATIONS FOR PANEL "B". PLEASE SEE | | | PANEL SCHEDULE INDICATES THREE CENTRAL | | | A/C SYSTEMS, 1-10KW AND TWO -5KW HEAT | | | STRIPS, PLEASE SEE LOAD CALCULATIONS | | | ONLY SHOW ONE 5KW UNIT? | | | PLEASE CORRELATE. | | | 215.5,220 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|