Plan Review Notes
Plan Review Notes For Permit 04090017
Permit Number 04090017
Review Stop B
Sequence Number 2
Notes
Date Text
2004-11-30 00:00:00DENIED
  
 1) THE WINDLOAD PRESSURES FOR THE
 BREAKFAST NOOK WINDOWS ARE GIVEN ON
 SHEET A-6 WITH THE ARROW POINTING TO
 THE
 WRONG LOCATION.
  
 2) ON SHEET A-5 TWO DIFFERENT SETS OF
 WINDLOAD PRESSURES ARE SPECIFIED FOR
 THE
 GOLF CART GARAGE DOOR. SEE FRONT AND
 LEFT ELEVATIONS. THE NEGATIVE PRESSURE
 GIVEN FOR THE DOOR ON THE LEFT
 ELEVATION
 EXCEEDS THE DESIGN PRESSURE ON THE
 PRODUCT APPROVAL.
  
 3) THE ATTIC ACCESS IN THE CEILING OF
 HIS WALK IN CLOSET ON THE FIRST FLOOR
 WILL NOT PROVIDE ACCESS TO THE ATTIC
 SPACE ABOVE THE MASTER SUITE BECAUSE IT
 IS LOCATED BELOW THE SECOND FLOOR
 BATHROOM. AN ACCESS THROUGH THE WALL OF
 THE SECOND FLOOR WALK IN CLOSET INTO
 THE
 ATTIC SPACE OF MASTER SUITE WOULD BE
 ADEQUATE.
  
 4) A LARGE PORTION OF THE SECOND FLOOR
 IS WOOD FRAME HOWEVER THE INSTALLATON
 SCHEDULE FOR THE STORM PANELS SPECIFIES
 CALK-IN FASTENERS WHICH ARE NOT FOR USE
 IN WOOD. PLEASE CORRECT.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714