Plan Review Notes
Plan Review Notes For Permit 04090017
Permit Number 04090017
Review Stop E
Sequence Number 1
Notes
Date Text
2004-09-20 00:00:00********* UNSAT *******
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 3)NOTE: PLEASE VERIFY OCP SHOWN FOR
 WHAT APPEARS TO BE A 5KW HEAT-STRIP IN
 AHU #2. SHOWN W/ 60A W/ #6 AWG.
 424.3B
  
 4)NOTE: PLEASE SEE NOTE #14 IN GENERAL
 NOTES. MENTIONS SD'S TO WIRED W/ BATH/
 KITCHEN LTS. PLEASE SEE 210.12 2002 NEC,
 THIS WOULD REQUIRE EITHER CIRCUIT TO BE
 ARC FAULT PROTECTED.
  
 5)NOTE: PLEASE SEE MASTER SUITE, RECEPT
 REQUIRED TO BE W/IN 6' OF DOOR.
 210.52
  
 **PLEASE SEE IDENTIFICATION OF SINGLE
 GARAGE SHOWN AS 3-CAR GARAGE. THIS IS
 ONLY A NOTE FOR WHAT APPEARS TO BE A
 MISPRINT.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 ONE SET OF OLD MAY BE SUBMITTED FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  