| Plan Review Notes For Permit 04090003 |
| Permit Number |
04090003 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2005-12-23 00:00:00 | MARC BROUGHT IN CALCS AND PROPOSAL | | | INDICATING THE COST WAS IN THE APPLIED | | | VALUE./WRT. | | 2005-12-22 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT A LOAD CALCULATION | | | INCLUDING THE ADDED LOADS. | | | | | | 2} INCREASE THE VALUE OF THE PROJECT TO | | | INCLUDE THE ADDED LABOR AND EQUIPMENT | | | ASSOCIATED WITH THIS REVISION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|