Plan Review Notes
Plan Review Notes For Permit 04090003
Permit Number 04090003
Review Stop P
Sequence Number 3
Notes
Date Text
2004-11-27 00:00:00DENIED
 REFERENCE; FBC-2001 CHAPTER 1
  
 1) THE SANITARY SYSTEM IS A SOVENT
 SYSTEM AND THE WATER CLOSET CAN NOT
 DISCHARGE DIRECTLY INTO THE STACK ON A
 SOVENT SYSTEM, BUT MUST CONNECT INTO THE
 AERATOR BELOW THE FLOOR OF THE UNIT
 BEING MODIFIED PER THE DESIGN CRITERIA
 OF THE SYSTEM. SECTION 104.2.1 AND
 DESIGN CRITERIS OF THE SOVENT SYSTEM
  
  
  
  
 REVIEW BY KEN STEVENS