Plan Review Notes
Plan Review Notes For Permit 04090003
Permit Number 04090003
Review Stop E
Sequence Number 2
Notes
Date Text
2005-03-08 00:00:00********** UNSAT **********
  
 1)NOTE: PLEASE SEE FROM PLANS SUBMITTED,
 COMPLETE SCOPE OF WORK HAS CHANGED FROM
 ORIGINAL PERMIT. IF SOME OF THIS WORK IS
 EXISTING, PLEASE SHOW.
 PLEASE SEE VLAUE FOR SCOPE OF WORK FROM
 ORIGINAL PERMIT APPLICATION SHALL
 INCREASE PER FBC 104.6.5.
  
 2)NOTE: PLEASE SEE ALL CHANGES TO PLANS
 MUST BE DONE BY THE ARCHITECT OF RECORD.
 PLEASE SEE PLANS MUST ALSO BE SIGNED ,
 DATED AND SEALED BY ARCH OF RECORD.
 PER FS 481.221
  
 PLEASE NOTE: IF REMODEL OF UNIT HAS
 EXCEEDED PERCENTAGE ALLOWED UNDER FBC
 CHAPTER 34, SUCH ITMES AS ARC FAULT
 PROTECTION MAY BE REQUIRED TO BE BROUGHT
 UP TO 2002 NEC 210.12.
 THIS BLDG WAS DONE UNDER 99 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]