Plan Review Notes
Plan Review Notes For Permit 04081476
Permit Number 04081476
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-05 00:00:00 
 THE ELECTRICAL SCHEMATIC SHOWS 1-1HP
 PUMP @ 30 AMPS & 1-2HP PUMP @50 AMPS.
 PLEASR CHECK NAMEPLATE FOR CORRECT
 AMPERAGES OR REFER TO TABLE 430.148
 NEC.
 PLEASE CORRECT AND RESUBMIT FOR REVIEW.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW