Plan Review Notes
Plan Review Notes For Permit 04081475
Permit Number 04081475
Review Stop E
Sequence Number 4
Notes
Date Text
2005-03-25 00:00:00****** PROVSIO/REVISION **********
  
  
 1)NOTE: PLEASE SEE 310.16, 3/0'S ARE
 ONLY RATED FOR 200A'S, YET MAIN
 DISCONNECT IS SHOWN AS 225A'S.
 PLEASE VEIRFY OCP/FUSES TO BE EITHER
 REDUCED TO 200A'S OR FEEDERS ARE TO BE
 RE-PULLED WITH 4/0'S PER 310.16,240.4
  
 THIS IS TO BE REVISEDALONG WITH ANY
 OTHER CHANGES BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  