| Plan Review Notes For Permit 04081475 |
| Permit Number |
04081475 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-03-25 00:00:00 | ****** PROVSIO/REVISION ********** | | | | | | | | | 1)NOTE: PLEASE SEE 310.16, 3/0'S ARE | | | ONLY RATED FOR 200A'S, YET MAIN | | | DISCONNECT IS SHOWN AS 225A'S. | | | PLEASE VEIRFY OCP/FUSES TO BE EITHER | | | REDUCED TO 200A'S OR FEEDERS ARE TO BE | | | RE-PULLED WITH 4/0'S PER 310.16,240.4 | | | | | | THIS IS TO BE REVISEDALONG WITH ANY | | | OTHER CHANGES BEFORE ROUGH ELECTRICAL | | | INSPECTION. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|