| Plan Review Notes For Permit 04081475 |
| Permit Number |
04081475 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-04-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | | | | 1) TOILET ROOM IN THE WAITING AREA DOES | | | NOT MEET CODE REQUIREMENTS FOR A 5' | | | TURNING AREA. THE W/C CAN NOT INTRUDE | | | INTO THE 5' TURNING AREA, AND TOILET | | | ROOM SHALL BE ENLARGED TO ACCOMODATE | | | THIS REQUIREMENT. SECTION 11-4.22.3 | | | 2) TOILET ROOMS SHALL BE ACCESSIBLE, | | | PLEASE INDICATE BY SHOWING THE FOLLOWING | | | INFORMATION: | | | A. CLEAR FLOOR SPACE 11-4.16.2 | | | B. TOILET HEIGHT 11-4.16.3 | | | C. GRAB BARS 11.4.16.4 | | | D. FLUSH CONTROLS 11-4.16.5 | | | E. DISPENSERS 11-4.16.6 | | | F. LAV HEIGHT & CLEARANCES 11-4.19.2 | | | G. LAV CLEAR FLOOR SPACE 11-4.19.3 | | | H. EXPOSED PIPES & SURFACES 11-4.19.4 | | | I. FAUCETS 11-4.19.5 | | | SUBMIT A DETAIL & SHOW CLEAR FLOOR SPACE | | | ON FLOOR PLAN. ALSO SHOW CLEAR FLOOR | | | SPACE FOR, (DRINKING FOUNTAIN OR WATER | | | COOLER), SEE FOLLOWING COMMENT. | | | 3) IF A DRINKING FOUNTAIN IS TO BE | | | INSTALLED, SANITARY PIPING AND WATER | | | PIPING SHALL BE SHOWN. IF THIS IS A | | | BOTTLED WATER COOLER THEN PIPING WILL | | | NOT BE REQUIRED. PLEASE CLARIFY. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|