Plan Review Notes
Plan Review Notes For Permit 04081475
Permit Number 04081475
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-10-13 00:00:00************DENIED**********************
  
 1) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE
 CONSTRUCTION SITE DAILY.
  
 3) WHAT ARE THE INTERIOR FINISH FOR THE
 WALLS AND CEILINGS, CLASS A, B OR C.
  
 4) SHEET #7 SHOWS NO FIRE SPRINKLER HEAD
 IN THE RESTROOMS, EXCEPTIONS ARE FOR
 DWELLING UNITS NOT BUSINESS OCCUPANCY.
  
 5) SEPARATE PLAN AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE SPRINKLER SYSTEMS
 REMODEL.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722