| 2004-10-14 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04081475 |
| | ADD: 5335 N MILITARY TRAIL# 49 |
| | CONT: TRICITY FLOORING INC |
| | TEL: (561)248-8329 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1)SHEET 1 OF 8 THE FURNISHING PLAN SHALL |
| | INDICATE THE ACCESSIBLE ROUTE THROUGH |
| | OUT THE TENANT SPACE.11-4.3.1 ALL WALKS, |
| | HALLS,CORRIDORS, AISLES & OTHER SPACES |
| | THAT ARE PART OF AN ACCESSIBLE ROUTE |
| | SHALL COMPLY WITH 11-4.3. |
| | |
| | 2) 11-4.3.3 WIDTH. THE MINIMUM CLEAR |
| | WIDTH OF AN ACCESSIBLE ROUTE SHALL BE |
| | 36" EXCEPT AT DOORS. SEE 11-4.13.5 AND |
| | 11-4.13.6. IF A PERSON IN A WHEELCHAIR |
| | MUST MAKE A TURN AROUND AN OBSTRUCTION, |
| | THE MINIMUM CLEAR WIDTH OF AN ACCESSIBLE |
| | ROUTE SHALL BE AS SHOWN IN FIGURE |
| | 7(A) AND (B). |
| | PROVIDE THE ACCESSIBLE PATH SHOWN ON |
| | THE FURNISHING PLAN, INDICATINGCLEAR |
| | FLOOR SPACE, MANEUVERING CLEARENCES AT |
| | DOORWAYS AND TURNS AROUND OBSTRUCTIONS, |
| | (DOORWAYS). |
| | |
| | 3) THE FRONT RESTROOM INDICATED AS AN |
| | HANDICAPPED RESTROOM IS MISSING THE GRAB |
| | BAR BEHIND THE WATERCLOSET, SEE FIGURE |
| | NO. 29. |
| | |
| | 4) REAR RESTROOM. 11-4.1.3(11) TO COMPLY |
| | WITH HANDICAPPED CODE. IF TOLIET ROOMS |
| | ARE PROVIDED, THEN EACH PUBLIC OR COMMON |
| | USE TOLIET ROOM SHALL COMPLY WITH |
| | 11-4.22. |
| | |
| | 5) SERVICE COUNTERS 11-7.2 SHALL HAVE A |
| | PORTION OF THE COUNTER WHICH IS 36" IN |
| | LENGTH WITH A MAXIMUM HEIGTH OF 36" |
| | ABOVE THE FLOOR. IT SHALL BE ON AN ACCES |
| | SIBLE ROUTE COMPLYING WITH 11-4.3. THE |
| | ACCESSIBLE COUNTERS MUST BE DISPERSED |
| | THROUGHOUT THE BUILDING OR FACILITY. |
| | |
| | 6) PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | ENGINEERS TO PROVIDE CERTIFICATE OF |
| | AUTHORIZATION FOR TURQUOISE CONSULTING |
| | INC. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |