2005-01-10 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW FOR THE UNDERGROUND PNEUMATIC
 PIPING:
 1.PROVIDE MANUFACTURER'S SUBMITTAL FOR
 THE FOR THE PNEUMATIC SYSTEM.
  
 2.INDICATE MATERIAL OF THE UNDERGROUND
 PIPE.
  
 3.PROVIDE SIZE OF THE UNDERGROUND
 PIPE.
  
 4.DEMONSTRATE SLEEVING FOR THE
 PIPING.
  
 5.PIPE SHALL HAVE A PRESSURE TEST
 BEFORE COVERING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  