| Plan Review Notes For Permit 04081457 |
| Permit Number |
04081457 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-11-08 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) EMPLOYEE LOUNGE SINK SHALL COMPLY | | | WITH SECTION 11-4.24 AND ALL | | | SUBSECTIONS | | | - NOT SHOWN WERE CLEAR FLOOR SPACE, AND | | | SINK DEPTH REQUIRED BY SECTIONS 4.24.4 | | | AND 4.24.5. | | | 3) SUBMIT MANUF. SPECIFICATION FOR INSTA | | | HOT WATER HEATER. INFORMATION SHALL SHOW | | | LISTING FOR HEATER. SECTION 303.4 | | | ******NEW COMMENT****** | | | 1B) SHT P2 OF 2 ONLY ONE COPY IS SEALED | | | BY THE ENGINEER OF RECORD. PER SECTION | | | 104.2.2 ALL COPIES SHALL BE | | | SIGNED/SEALED/DATED. | | | 2B) REMOVE ALL VOIDED SHEETS AND SUBMIT | | | ONE SET SEPARATE FROM SETS TO BE | | | REVIEWED FOR COMPAIRSON. SECTION | | | 104.2.1 | | | 3B) NOT ALL SHEETS HAVE A RAISED SEAL. | | | ALL SHEETS SUBMITTED FOR PUBLIC RECORD | | | SHALL HAVE A RAISED SEAL. SOME SHEETS | | | HAVE A PHOTO COPY OF THE SEAL. | | | | | | |
|