Plan Review Notes
Plan Review Notes For Permit 04081457
Permit Number 04081457
Review Stop P
Sequence Number 1
Notes
Date Text
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) EMPLOYEE LOUNGE SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS
 SHOW HEIGHT 11-4.24.2, KNEE CLEARANCE
 11-4.24.3, SINK DEPTH 11-4.24.4, CLEAR
 FLOOR SPACE 11-4.24.5 SHALL BE PROVIDED
 INFRONT OF SINK TO ALLOW FORWARD APPROA-
 CH, EXPOSED PIPES AND SURFACES 11-4.24.6
  
 2) SHT P2 OF 2, WATER RISER DIAGRAM. THE
 WATER HAMMER ARRESTOR SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALL. INSTRUCTIONS.
  
 3) SUBMIT MANUF. SPECIFICATION FOR INSTA
 HOT WATER HEATER. INFORMATION SHALL SHOW
 LISTING FOR HEATER. SECTION 303.4
  
 REVIEW BY KEN STEVENS