| Plan Review Notes For Permit 04081457 |
| Permit Number |
04081457 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) EMPLOYEE LOUNGE SINK SHALL COMPLY | | | WITH SECTION 11-4.24 AND ALL SUBSECTIONS | | | SHOW HEIGHT 11-4.24.2, KNEE CLEARANCE | | | 11-4.24.3, SINK DEPTH 11-4.24.4, CLEAR | | | FLOOR SPACE 11-4.24.5 SHALL BE PROVIDED | | | INFRONT OF SINK TO ALLOW FORWARD APPROA- | | | CH, EXPOSED PIPES AND SURFACES 11-4.24.6 | | | | | | 2) SHT P2 OF 2, WATER RISER DIAGRAM. THE | | | WATER HAMMER ARRESTOR SHALL BE LOCATED | | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | | NOT IN THE CEILING AS SHOWN. PDI-WH 201 | | | AND MANUF. INSTALL. INSTRUCTIONS. | | | | | | 3) SUBMIT MANUF. SPECIFICATION FOR INSTA | | | HOT WATER HEATER. INFORMATION SHALL SHOW | | | LISTING FOR HEATER. SECTION 303.4 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|