| Plan Review Notes For Permit 04081457 |
| Permit Number |
04081457 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-09-22 00:00:00 | DENIED: | | | 1.PLAN SHEET AC-1 INDICATES AN AC-2 | | | PLAN WHICH WAS NOT SUBMITTED.PLEASE | | | CLARIFY. | | | | | | 2.HVAC NOTES #8 REFERS TO FIRE DAMPERS | | | PENETRATING FIRE WALLS.IS THIS ARE THE | | | STORAGE ROOM?THE ARCHITECTURAL PLANS | | | DO NOT INDICATE FIRE WALLS ON PLAN | | | SHEET A-3, BUT DOES GIVE A DETAIL ON | | | A-6. | | | | | | 3.SOME OF THE DIFFUSERS ARE MARKED | | | "E" (EXISTING).ARE THE DIFFUSERS NOT | | | MARKED NEW OR RELOCATED? | | | | | | 4.NO COMBUSTIBLES ALLOWED ABOVE THE | | | CEILING IN THE RETURN AIR PLENUM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|