Plan Review Notes
Plan Review Notes For Permit 04081457
Permit Number 04081457
Review Stop M
Sequence Number 1
Notes
Date Text
2004-09-22 00:00:00DENIED:
 1.PLAN SHEET AC-1 INDICATES AN AC-2
 PLAN WHICH WAS NOT SUBMITTED.PLEASE
 CLARIFY.
  
 2.HVAC NOTES #8 REFERS TO FIRE DAMPERS
 PENETRATING FIRE WALLS.IS THIS ARE THE
 STORAGE ROOM?THE ARCHITECTURAL PLANS
 DO NOT INDICATE FIRE WALLS ON PLAN
 SHEET A-3, BUT DOES GIVE A DETAIL ON
 A-6.
  
 3.SOME OF THE DIFFUSERS ARE MARKED
 "E" (EXISTING).ARE THE DIFFUSERS NOT
 MARKED NEW OR RELOCATED?
  
 4.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM.
  