| 2005-06-08 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | AS NOTED IN THE TWO PREVIOUS REVIEWS, |
| | THE OPTIONAL STANDBY SYSTEM (GENERATOR |
| | AND RELATED EQUIPMENT) MUST BE APPLIED |
| | FOR UNDER A SEPERATE PERMIT. SEE |
| | REQUIREMENTS, PRIOR REVIEW. |
| | |
| | REVISIONS TO THE PLANS MUST BE MADE BY |
| | THE ARCHITECT, HANDRAWN CHANGES ARE |
| | UNACCEPTABLE. SEE FS 481. |
| | |
| | THE PANEL SCHEDULES DO NOT CORRELATE TO |
| | THE CIRCUIT NUMBERS ON THE PLAN. SEE |
| | D-16, PLEASE CHECK ALL PRIOR TO |
| | RESUBMITTING. |
| | |
| | NOTE 3 FROM PRIOR, GEC STILL INCORRECT. |
| | SEE 250.66. NOTE: SERVICE INCREASED |
| | AGAIN, PLEASE LOOK AT REFERANCE THE |
| | TABLE INDICATED FOR PROPER SIZE. |
| | |
| | RECEPTACLE B-3 IN THE MASTER BEDROOM IS |
| | IN VIOLATION OF 210.11(C)(3). |
| | |
| | THIS REVISION IS BEING DENIED BECAUSE |
| | THE GENERATOR APPEARS AS PART OF THIS |
| | REVISION. ALL ITEMS NEED TO BE ADDRESSED |
| | ON RESUB. |
| | |
| | THE ORIGINAL VALUE MUST BE INCREASED TO |
| | REFLECT THE ADDITIONAL WORK. PLEASE SEE |
| | PERMIT CLERK WITH NEW VALUE AT TIME OF |
| | RESUBMITION. FEES MUST BE PAID PRIOR TO |
| | REVIEW. SEE 553.80 FS. |
| | |
| | PLEASE PROVIDE A SCHEMATIC OF THE |
| | ELECTRICAL SYSTEM FOR THE POOL WITH THAT |
| | PERMIT APPLICATION (TYPICAL). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |