Plan Review Notes
Plan Review Notes For Permit 04081385
Permit Number 04081385
Review Stop E
Sequence Number 6
Notes
Date Text
2005-06-08 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 AS NOTED IN THE TWO PREVIOUS REVIEWS,
 THE OPTIONAL STANDBY SYSTEM (GENERATOR
 AND RELATED EQUIPMENT) MUST BE APPLIED
 FOR UNDER A SEPERATE PERMIT. SEE
 REQUIREMENTS, PRIOR REVIEW.
  
 REVISIONS TO THE PLANS MUST BE MADE BY
 THE ARCHITECT, HANDRAWN CHANGES ARE
 UNACCEPTABLE. SEE FS 481.
  
 THE PANEL SCHEDULES DO NOT CORRELATE TO
 THE CIRCUIT NUMBERS ON THE PLAN. SEE
 D-16, PLEASE CHECK ALL PRIOR TO
 RESUBMITTING.
  
 NOTE 3 FROM PRIOR, GEC STILL INCORRECT.
 SEE 250.66. NOTE: SERVICE INCREASED
 AGAIN, PLEASE LOOK AT REFERANCE THE
 TABLE INDICATED FOR PROPER SIZE.
  
 RECEPTACLE B-3 IN THE MASTER BEDROOM IS
 IN VIOLATION OF 210.11(C)(3).
  
 THIS REVISION IS BEING DENIED BECAUSE
 THE GENERATOR APPEARS AS PART OF THIS
 REVISION. ALL ITEMS NEED TO BE ADDRESSED
 ON RESUB.
  
 THE ORIGINAL VALUE MUST BE INCREASED TO
 REFLECT THE ADDITIONAL WORK. PLEASE SEE
 PERMIT CLERK WITH NEW VALUE AT TIME OF
 RESUBMITION. FEES MUST BE PAID PRIOR TO
 REVIEW. SEE 553.80 FS.
  
 PLEASE PROVIDE A SCHEMATIC OF THE
 ELECTRICAL SYSTEM FOR THE POOL WITH THAT
 PERMIT APPLICATION (TYPICAL).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026