Plan Review Notes For Permit 04081385
Permit Number 04081385
Review Stop E
Sequence Number 4
Notes
Date Text
2005-04-12 00:00:00*********** UNSAT ***************
  
 PLEASE SEE PLANS HAVE UNDERGONE MANY
 CHANGES SINCE PREVIOUS STAMPED PLANS.
 PLEASE SEE THE BELOW COMMENTS PERTAINING
 TO CHANGES.
  
  
 1)NOTE: PLEASE SEE PLANS NOW SHOW A NEW
 PROPOSED GENERATOR. PLEASE SEE THIS IS
 REQUIRED TO BE SUBMITTED UNDER A
 SEPARATE PERMIT. THIS WILL REQUIRE SITE
 PLANS, COMPLETE RISER DIAGRAM,
 MANUFACTURE SPECS FOR GEN, ATS,
 PRIMEMOVER ETC.
 THIS WILL BE REVIEWED BY, ZONING, BLDG,
 PLUMB, MECH AND BLDG REVIEW ALL UNDER
 ONE PERMIT.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM FOR
 MAIN HOUSE PLANS WILL BE REQUIRED TO BE
 REVISED TO INCLUDE ALL NEW ELECTRICAL
 SERVICE EQUIPMENT. PLEASE SEE RISER DOES
 NOT INDICATE ANY ATS ETC AT THIS TIME.
  
 3)NOTE: PLEASE SEE SERVICE SIZE HAS NOW
 CHNAGED AND INCREASED TO 325A.
 PLEASE SEE MIN GROUNDING ELECTRODE
 CONDUCTOR PER 250.66. #2 MIN.
  
 4)NOTE: PLEASE SEE MIN CLEARENCE FOR
 PANEL "C" NOT SHOWN. 110.26
  
 5)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE SEE MANY RECESSED LTS WERE ADDED,
 HOWEVER, NO ADDITIONAL LOADS PER ABOVE
 WAS ADDED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  