| 2005-04-20 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1) SHT M-1 SANITARY RISER DIAGRAMS DO |
| | NOT MEET CODE REQUIREMENTS, NOR DO THEY |
| | REFLECT THE FLOOR PLAN. CORRECT THE |
| | FOLLOWING: |
| | A. KITCHEN SINK RISER INDICATES TO |
| | EXISTING 3" MAIN, BUT FLOOR PLAN STATES |
| | EXISTING 4" SAN. PLEASE CORRELATE RISER |
| | AND FLOOR PLAN. SECTION 104.2.1. |
| | B. MASTER BATH RISER SHOWS A HORIZONTAL |
| | DRY VENT. THIS IS NOT APPROVED PER |
| | SECTIONS 905.3 & 905.4. |
| | C. UTILITY ROOM RISER SHOWS A BRANCH |
| | ARM TO "US" FIXTURE ABOVE THE WASH |
| | MACHINE DRAIN LINE. THIS IS NOT SHOWN ON |
| | THE FLOOR PLAN. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 2) NEW GENERATOR SHOWN ON PLANS. A |
| | RES-GEN PERMIT IS REQUIRED. A SURVEY |
| | SHOWING THE LOCATION OF THE GENERATOR IS |
| | REQUIRED. SHOW THE LOCATION OF ALL |
| | OPENINGS IN THE HOUSE AND SHOW THE |
| | LOCATION OF ADJOINING PROPERTY LINE AND |
| | THE LOCATION OF STRUCTURES ON ADJOINING |
| | PROPERTY. A BUILDING, ZONING, |
| | MECHANICAL, ELECTRICAL, & GAS REVIEW |
| | WILL BE REQUIRED. |
| | 3) SEPARATE GAS PLANS & PERMIT ARE |
| | REQUIRED. SEE ATTACHED SHEET SHOWING GAS |
| | PERMIT APPLICATION REQUIREMENTS. THESE |
| | REQUIREMENTS SHALL BE SUBMITTED WITH THE |
| | APPLICATION FOR THE GAS PERMIT. |
| | |