2005-04-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) SHT M-1 SANITARY RISER DIAGRAMS DO
 NOT MEET CODE REQUIREMENTS, NOR DO THEY
 REFLECT THE FLOOR PLAN. CORRECT THE
 FOLLOWING:
 A. KITCHEN SINK RISER INDICATES TO
 EXISTING 3" MAIN, BUT FLOOR PLAN STATES
 EXISTING 4" SAN. PLEASE CORRELATE RISER
 AND FLOOR PLAN. SECTION 104.2.1.
 B. MASTER BATH RISER SHOWS A HORIZONTAL
 DRY VENT. THIS IS NOT APPROVED PER
 SECTIONS 905.3 & 905.4.
 C. UTILITY ROOM RISER SHOWS A BRANCH
 ARM TO "US" FIXTURE ABOVE THE WASH
 MACHINE DRAIN LINE. THIS IS NOT SHOWN ON
 THE FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
 2) NEW GENERATOR SHOWN ON PLANS. A
 RES-GEN PERMIT IS REQUIRED. A SURVEY
 SHOWING THE LOCATION OF THE GENERATOR IS
 REQUIRED. SHOW THE LOCATION OF ALL
 OPENINGS IN THE HOUSE AND SHOW THE
 LOCATION OF ADJOINING PROPERTY LINE AND
 THE LOCATION OF STRUCTURES ON ADJOINING
 PROPERTY. A BUILDING, ZONING,
 MECHANICAL, ELECTRICAL, & GAS REVIEW
 WILL BE REQUIRED.
 3) SEPARATE GAS PLANS & PERMIT ARE
 REQUIRED. SEE ATTACHED SHEET SHOWING GAS
 PERMIT APPLICATION REQUIREMENTS. THESE
 REQUIREMENTS SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE GAS PERMIT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]