Plan Review Notes
Plan Review Notes For Permit 04081385
Permit Number 04081385
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-17 00:00:00********* UNSAT ** 2ND REVIEW ********
  
 SOME NOTES FROM FIRST REVIEW STILL TO BE
 ADDRESSED.
  
  
 1)NOTE: PLEASE SHOW ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE(S) AS
 GFI/GFI PROTECTED PER 210.8A-6
 PLEASE SEE 210.52C1 FOR RECEPT SPACING.
  
 2)NOTE: PLEASE SEE OCP FOR AHU'S/ HEAT.
 PLEASE SEE 424.3B FOR SIZING @125%.
 MIN)
  
 3)NOTE: PLEASE SEE NOTES ON LOWER LEFT
 ARE NOW NOTEING 2000 NEC. ? MISPRINT?
 PLEASE SEE NOTE #22 MENTIONS ARC FAULT
 PROTECTION FOR RECEPTS ONLY.
 PLANS DO HAVE NOTE UNDER PANEL SCHEDULE
 FOR 210.12
 *** NOTE*** PLEASE SEE NOTE #20 STILL
 MENTIONS SD'S TO BE WIRED TO KIT AND
 BATH LT CIRCUITS. PLEASE SEE THAT THIS
 IS FINE AND PERMITTED BY CODE, HOWEVER,
 THEN THESE CIRCUITS ARE ALSO REQUIRED TO
 HAVE THE ARC FAULT PROTECTION. 210.12
 THIS IS ONLY A NOTE**
  
 4)NOTE: PLEASE SEE MCB PANEL INDICATES A
 250A MCB YET PANEL INDICATES A 200A
 BUS?
 PLEASE CORRELATE.
  
 5)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS. THIS REQUIRES 1ST 8KW AT
 100% AND REMAINDER @40%. THE 100% FOR
 A/C HEAT LOAD WAS CORRECTED.
  
 6)NOTE: PLEASE SEE AIC CALCULATION IS
 SHOWN IN THE UPPER LEFT HAND CORNER OF
 PLANS WHICH INDICATES A 12,781 AVAILABLE
 FUALT CURRENT AT MAIN YET MCB PANEL IS
 SHOWN W/ AND 10,000 RATED MAIN? PLEASE
 CORRELATE. THIS PANEL "A" WOULD REQUIRE
 A 22,000 AIC RATING MIN.
 110.9
  
 7)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL. THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME.
  
  
 PLEASE REMOVE OLD SHEETS AND INSERT ONLY
 NEW SHEETS INTO COMPLETE SETS FOR REVIEW
 AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW