Plan Review Notes
Plan Review Notes For Permit 04081385
Permit Number 04081385
Review Stop E
Sequence Number 1
Notes
Date Text
2004-09-16 00:00:00********* UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 3) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
 PLEASE SEE BOTH STAIRS
  
 5 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 6)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU HEAT. MIN 125%.
 30A SHOWN FOR 7.5KW
  
 7)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS.
 PLEASE ALSO CORRELATE LOADS ON EACH
 PANEL/ LOAD CALCS/ AND MDP.
  
 8 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
 PLEASE ALSO SEE NOTES FOR SD'S ON KIT/
 BATH LT-ING CIRCUIT.
  
 9)NOTE: PLEASE SEE THERE ARE NOTES
 REFLECTING OLD CODE. PLEASE ADJUST NOTES
 AND CODES PER 2002 NEC.
 THE STATE ADOPTED THE 2002 NEC JULY 1ST,
 2003
  
 10)NOTE: PLEASE SEE 210.11C1, 220.16
 A MIN OF 2-SMALL APPLIANCE CIRCUITS
 REQUIRED. APPEARS TO SHOW ONE?
 MISPRINT?
  
 11)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved