| Date |
Text |
| 2004-09-16 00:00:00 | ********* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 3) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2 |
| | PLEASE SEE BOTH STAIRS |
| | |
| | 5 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 6)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU HEAT. MIN 125%. |
| | 30A SHOWN FOR 7.5KW |
| | |
| | 7)NOTE: PLEASE SEE 220.31B FOR LOAD |
| | CALCULATIONS. |
| | PLEASE ALSO CORRELATE LOADS ON EACH |
| | PANEL/ LOAD CALCS/ AND MDP. |
| | |
| | 8 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC 210.12 |
| | PLEASE ALSO SEE NOTES FOR SD'S ON KIT/ |
| | BATH LT-ING CIRCUIT. |
| | |
| | 9)NOTE: PLEASE SEE THERE ARE NOTES |
| | REFLECTING OLD CODE. PLEASE ADJUST NOTES |
| | AND CODES PER 2002 NEC. |
| | THE STATE ADOPTED THE 2002 NEC JULY 1ST, |
| | 2003 |
| | |
| | 10)NOTE: PLEASE SEE 210.11C1, 220.16 |
| | A MIN OF 2-SMALL APPLIANCE CIRCUITS |
| | REQUIRED. APPEARS TO SHOW ONE? |
| | MISPRINT? |
| | |
| | 11)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |