| Plan Review Notes For Permit 04081380 |
| Permit Number |
04081380 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-03-01 00:00:00 | REVISION CHECKLIST: | | | 1- ROOF STRUCTURE WAS DESIGNED TO CARRY | | | SHINGLES. PRODUCT APPROVAL SUBMITTED IS | | | FOR CLAY TILE. ENGINEER OF RECORD TO | | | REVISE PLANS/SPECS TO REFLECT ADDITIONAL | | | ROOF LOAD. | | | | | | 2- ENGINEER OF RECORD TO SPECIFY ROOF | | | TILE FASTENING AS REQUIRED BY SECTION | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT 805-6712. |
|