Plan Review Notes
Plan Review Notes For Permit 04081357
Permit Number 04081357
Review Stop E
Sequence Number 4
Notes
Date Text
2005-06-24 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASE CORRECT ADDRESSING ON
 PLANS ETC. PLEASE SEE THIS WAS NOTED ON
 ALL PREVIOUS REVIEWS, YET PLANS ETC
 STILL HAVE NOT BEEN CORRECTED OR
 CHANGED.
 PLEASE SEE PERMIT IS ISSUEED UNDER 365
 PLYMOUTH RD, PLANS DETAIL 367 AND
 REVISION COVER SHEET FILLED OUT BY CONT
 HAS 375????
 PLEASE CORRELATE.
 FAC 61G1-16.004
  
 2)NOTE: PLEASE SEE TITLE BLOCKS ARE
 REQUIRED TO IDENTIFY ALL REV'S WITH
 CLOUDS AND TRIANLGES. PLEASE SEE THE
 LAST REV DATE IS NOTED AS OCT 04.
  
 3)NOTE: PLEASE SEE 110.26,408.7 ETC,
 PANELS IN STORAGE AREA. THIS RM/AREA
 SHALL BE DESIGNATED AS MECH/ELEC RM. NO
 STORAGE PERMITTED WITH CLOSE PROXIMITY
 TO EASILY IGNITIBLE MATERIALS.
 PLANS TO IDENTIFY AS ABOVE.
  
 4)NOTE: PLEASE SEE 210.52C1 FOR WHAT
 APPEARS TO BE MISSING GFI ALONG KITCHEN
 COUNTERSPACE.
 PLEASE SEEAREA RDLINED ON PLANS???
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved