| Date |
Text |
| 2004-09-15 00:00:00 | ******** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE 210.52C1 FOR RECEPTS |
| | ALONG KITCHEN COUNTERSPACE. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | PLEASE LIST AS 20A, #12 |
| | |
| | 4)NOTE:SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE ALSO SEE NFPA-72 8-1.4.2 FOR |
| | SD'S W/IN 20' OF COOKING APPLIANCE. |
| | |
| | 5)NOTE: PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 6)NOTE: PLEASE SEE 250.32 FOR GRND AT |
| | DEATCHED BLDG TO BE ATTACHED TO FOOTER |
| | STEEL/ ANY METAL CWP. |
| | |
| | 7)NOTE: PLEASE SEE RISER INDICATES AN |
| | EQUIPMENT GROUNDING CONDUCTOR FROM METER |
| | TO MAIN (FIRST MEANS OF DISC). |
| | THIS IS NOT PERMITTED. 250.6 ONLY AFTER |
| | THE FIRST MEANS OF DISC. 250.24 |
| | |
| | 8)NOTE: PLEASE SEE MISSING RECEPT FOR |
| | 2' OF WALL SPACE IN BEDRM UPSTAIRS. |
| | 210.52 |
| | |
| | 9)NOTE: PLEASE SEE SMALL APPLIANCE |
| | CIRCUITS SHOWN W/ A LOADOF 3KW EACH. |
| | MAX LOAD ON A 20A CIRCUIT WOULD BE 1.9KW |
| | MIN REQUIRED BY 210.11C1,220.16A |
| | |
| | 10)NOTE: PLEASE SEE KW LOADS SHOWN FOR |
| | EACH AHU HEAT. EACH @ 5KW? AS SHOWN ON |
| | MECH? PLEASE SEE OCP SHOWN AT 40A. |
| | PLEASE VERIFY. 424.3B MIN OCP IS 125% |
| | OF KW RATING AND MAX 150%. |
| | PLEASE ALSO SEE LOAD SHOWN FOR WATER |
| | HEATERS ARE AT 4KW EACH. PLEASE VERIFY |
| | KW RATING AS IT DOES NOT SEEM TO BE A |
| | COMMON SIZE. PLEASE SEE MIN OCP TO ALSO |
| | BE 125% 422.13 |
| | |
| | 11)NOTE: PLEASE PROVIDE ROOM DESIGNATION |
| | ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD SHEETS AND ONLY |
| | INSERT NEW SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. ONE SET OF OLD |
| | SHEETS MAY BE REQUIRED FOR REFERENCE |
| | ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |