| Plan Review Notes For Permit 04081284 |
| Permit Number |
04081284 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2005-09-02 00:00:00 | STORM PANEL SUBMITTAL DENIED | | | | | | 1) THE MEAN ROOF HEIGHT ON THE KEY PLAN | | | IS INCORRECTLY LISTED AS 12'. THE MEAN | | | ROOF HEIGHT IS 16' AS SPECIFIED ON THE | | | PLANS. | | | | | | 2) THE KEY PLAN IS MISSING THE 2-25SH | | | WINDOWS AT THE REAR OF THE FAMILY ROOM. | | | PLEASE CORRECT. | | | | | | 3) THE DOOR AT THE FAMILY ROOM INDICATED | | | AS THE EMERGENCY ESCAPE DOOR REQUIRED BY | | | FBC 1005.4.5 ON THE KEY PLAN IS | | | SPECIFIED AS A SLIDING GLASS DOOR ON THE | | | PLANS. THE PRODUCT APPROVAL THAT YOU | | | SUBMITTED IS FOR A DOUBLE SWINGING DOOR. | | | THE SIGNED AND SEALED PLANS WILL NEED TO | | | BE CHANGED FROM A SLIDING GLASS DOOR TO | | | A DOUBLE SWINGING DOOR BY SUBMITTING | | | REVISED PLANS. PLEASE BE AWARE THAT THIS | | | ESCAPE AND RESCUE OPENING CAN BE AN | | | IMPACT RESISTANT WINDOW THAT COMPLIES | | | WITH THE REQUIREMENTS OF FBC 1005.4 FOR | | | SLEEPING ROOMS AS LONG AS IT IS LOCATED | | | IN A ROOM THAT DOES NOT REQUIRE THE | | | OCCUPANTS OF THE HOME TO PASS THROUGH A | | | LOCKABLE DOOR NOT UNDER THEIR CONTROL. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|