2005-09-02 00:00:00STORM PANEL SUBMITTAL DENIED
  
 1) THE MEAN ROOF HEIGHT ON THE KEY PLAN
 IS INCORRECTLY LISTED AS 12'. THE MEAN
 ROOF HEIGHT IS 16' AS SPECIFIED ON THE
 PLANS.
  
 2) THE KEY PLAN IS MISSING THE 2-25SH
 WINDOWS AT THE REAR OF THE FAMILY ROOM.
 PLEASE CORRECT.
  
 3) THE DOOR AT THE FAMILY ROOM INDICATED
 AS THE EMERGENCY ESCAPE DOOR REQUIRED BY
 FBC 1005.4.5 ON THE KEY PLAN IS
 SPECIFIED AS A SLIDING GLASS DOOR ON THE
 PLANS. THE PRODUCT APPROVAL THAT YOU
 SUBMITTED IS FOR A DOUBLE SWINGING DOOR.
 THE SIGNED AND SEALED PLANS WILL NEED TO
 BE CHANGED FROM A SLIDING GLASS DOOR TO
 A DOUBLE SWINGING DOOR BY SUBMITTING
 REVISED PLANS. PLEASE BE AWARE THAT THIS
 ESCAPE AND RESCUE OPENING CAN BE AN
 IMPACT RESISTANT WINDOW THAT COMPLIES
 WITH THE REQUIREMENTS OF FBC 1005.4 FOR
 SLEEPING ROOMS AS LONG AS IT IS LOCATED
 IN A ROOM THAT DOES NOT REQUIRE THE
 OCCUPANTS OF THE HOME TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  