2004-12-03 00:00:00********* UNSAT *************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 THIS RATING IS REQUIRED ON PLANS FOR
 EQUIPMENT TO BE INSTALLED.
 FIRST REVIEW NOTES:
  
 2)NOTE: PLEASE SEE ENTIRE AREA OF HAND-
 -DRAWN CHANGES AND ITEMS ON PLANS.
 PLEASE SEE FS 471.025 THIS IS NOT
 PERMITTED ON PLANS WHICH ARE SIGNED,
 DATED AND SEALED BY AN ENGINEER.
 PLEASE HAVE PLANS RE-PRINTED AND
 RE-SIGNED, DATED AND SEALED BY
 ENGINEER.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  