| Date |
Text |
| 2004-08-31 00:00:00 | ************ UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR |
| | MISSING INFORMATION REQUIRED ON TITLE |
| | BLOCK FOR ENGINEER OF RECORD. |
| | FS 471.025 |
| | PLEASE ALSO SIGN WITH COMPLETE "LEGAL" |
| | SIGNATURE. PLANS APPEAR TO HAVE INITIALS |
| | WHICH ARE NOT ACCEPTABLE. |
| | THIS IS REQUIRED ON ALL SHEETS WHEATHER |
| | OR NOTE COMMENT COMES FROM OTHER REVIEW- |
| | -ERS. |
| | PLEASE ALSO SEE FBC 104.2.1 |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3) NOTE: PLEASE SHOW GROUNDING ELETRODE |
| | SYSTEM PER 250.50. FOOTER STEEL/COLD |
| | WATER/ ETC. SIZE ALL PER 250.66 |
| | |
| | 4 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 5)NOTE: PLEASE SEE AHU/HEAT LOAD SHOWN |
| | AT 2KW. PLEASE CORRELATE OCP/AWG AND |
| | KW LOAD SHOWN ON MECH PLANS. |
| | PLEASE SEE 424.3B FOR OCP. |
| | |
| | 6)NOTE: PLEASE SHOW LOAD CALCULATIONS W/ |
| | OUT ASSUMED LOAD OF PANELS B AND C. |
| | |
| | 7)NOTE: PLEASE PROVIDE INFORMATION ON |
| | MAIN?? NONE INDICATED. SIZE, ETC. |
| | 225.31 |
| | |
| | |
| | 8)NOTE: PLEASE SHOW A/C EQUIPMENT ON |
| | PLANS. |
| | DISC MEANS PER 440.11 |
| | RECEPT PER 210.63 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |