2004-08-31 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING INFORMATION REQUIRED ON TITLE
 BLOCK FOR ENGINEER OF RECORD.
 FS 471.025
 PLEASE ALSO SIGN WITH COMPLETE "LEGAL"
 SIGNATURE. PLANS APPEAR TO HAVE INITIALS
 WHICH ARE NOT ACCEPTABLE.
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOTE COMMENT COMES FROM OTHER REVIEW-
 -ERS.
 PLEASE ALSO SEE FBC 104.2.1
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3) NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 4 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 5)NOTE: PLEASE SEE AHU/HEAT LOAD SHOWN
 AT 2KW. PLEASE CORRELATE OCP/AWG AND
 KW LOAD SHOWN ON MECH PLANS.
 PLEASE SEE 424.3B FOR OCP.
  
 6)NOTE: PLEASE SHOW LOAD CALCULATIONS W/
 OUT ASSUMED LOAD OF PANELS B AND C.
  
 7)NOTE: PLEASE PROVIDE INFORMATION ON
 MAIN?? NONE INDICATED. SIZE, ETC.
 225.31
  
  
 8)NOTE: PLEASE SHOW A/C EQUIPMENT ON
 PLANS.
 DISC MEANS PER 440.11
 RECEPT PER 210.63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]