| Plan Review Notes For Permit 04081257 |
| Permit Number |
04081257 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-06 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | | | 1. THE ENERGY CODE FORM HAS TO BE SIGNED | | | BY THE OWNER/AGENT. | | | | | | 2. THE THERMA-TRU DOORS REQUIRE | | | HURRICANE PANELS. NO INFORMATION HAS | | | BEEN SUBMITTED FOR THE STORM PANELS. | | | | | | 3. THERE ARE NO PRODUCT APPROVALS FOR | | | THE SINGLE HUNG WINDOWS. | | | | | | 4. THE FIXED WINDOWS UNDER 30' WILL | | | REQUIRE HURRICANE PANELS. | | | | | | 5. A NOTICE OF COMMENCEMENT MUST BE | | | FILED AT THE PBC CLERK'S OFFICE AND A | | | COPY SUBMITTED BEFORE A PERMIT CAN BE | | | PRINTED | | | | | | 6. THERE ARE ADDITIONAL FEES OF | | | $1865.11DUE. | | | | | | 7. SUBMIT THE REQUIRED PRODUCT APPROVALS | | | FOR THE STORM PANELS. | | | | | | 8. THE LICENSES FOR THE A/C & BUILDING | | | CONTRACTOR HAVE EXPIRED. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|