| Plan Review Notes For Permit 04081247 |
| Permit Number |
04081247 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-11-18 00:00:00 | ****** UNSAT 2ND REVIEW ****** | | | | | | PLEASE SEE SOME NOTES FROM FIRST REVIEW | | | STILL NEED TO BE ADDRESSED. | | | | | | 1)NOTE:PLEASE SEE NOTE #5, PANEL | | | SCHEDULES SHOWN, HOWEVER NO LOAD | | | CALCULATIONS, RISER ETC HAVE BEEN | | | SUBMITTED. | | | PREVIOUS PLANS CALLED FOR NEW 100A | | | PANEL, HOWEVER THESE PLANS ARE NOW | | | CALLING FOR 125A PANELS. | | | PLEASE PROVIDE INFORMATION ON THE NEW PR | | | EXSITING FEEDS FOR THESE PANELS. OCP, | | | AWG, CONDUIT SIZES ETC. | | | | | | 2)NOTE: PLEASE SEE 210.52D,210.11C3 FOR | | | MIN 20A #12 CIRCUITS REQUIRED FOR BATH | | | GFI'S. PANEL SCHEDULE INDICATES 15A, | | | #14. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWERS WHICH MAY AFFETC | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT NEW INTO TWO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|