Plan Review Notes For Permit 04081247
Permit Number 04081247
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-18 00:00:00****** UNSAT 2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
  
 1)NOTE:PLEASE SEE NOTE #5, PANEL
 SCHEDULES SHOWN, HOWEVER NO LOAD
 CALCULATIONS, RISER ETC HAVE BEEN
 SUBMITTED.
 PREVIOUS PLANS CALLED FOR NEW 100A
 PANEL, HOWEVER THESE PLANS ARE NOW
 CALLING FOR 125A PANELS.
 PLEASE PROVIDE INFORMATION ON THE NEW PR
 EXSITING FEEDS FOR THESE PANELS. OCP,
 AWG, CONDUIT SIZES ETC.
  
 2)NOTE: PLEASE SEE 210.52D,210.11C3 FOR
 MIN 20A #12 CIRCUITS REQUIRED FOR BATH
 GFI'S. PANEL SCHEDULE INDICATES 15A,
 #14.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFETC
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW INTO TWO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  