| 2004-10-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) BOTH SETS OF PLANS SHALL BE SIGNED, |
| | SEALED AND DATED BY THE ARCHITECT OF |
| | RECORD, AND SEAL SHALL SHOW ALL INFORM- |
| | ATION REQUIRED BY FAC 61G1-16.001 AND |
| | FS 481.221. |
| | 2) TITLE BLOCK ON ALL SHEETS SHALL HAVE |
| | THE MINIMUM INFORMATION. FIRM LICENSE |
| | NUMBER, & SPACE FOR PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. FAC 61G1-16 |
| | .004(2) & (6). FS 481.2055 |
| | 3) A CERTIFICATE OF AUTHROIZATION NUMBER |
| | IS REQUIRED FOR THE ARCHITECTURAL COMP- |
| | ANY PER FS481.219 |
| | 4) SHT A-2 DEMO SHEET, IN THE INSTALLAT- |
| | ION OR REMOVAL OF ANY PART OF A DRAINAGE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| | SECTION 704.5. - ALL CAPPED PIPING SHALL |
| | BE INSPECTED PRIOR TO COVERING. |
| | 5) SHT A-6 DETAIL 6 MASTER BATH SHOWER |
| | SHOWS 28" WIDTH. SECTION 417.4 STATES, |
| | SHOWER COMPARTMENTS SHALL NOT BE LESS |
| | THAN 30" IN MINIMUM DIMENSION MEASURED |
| | FROM THE FINISHED INTERIOR DIMENSION AND |
| | SHALL BE MEASURED AS THE SIDE OF A REC- |
| | TANGLE. |
| | 6) SHT M-1 PLUMBING NOTES 9 AIR CHAMBERS |
| | ARE NOT APPROVED. DELETE FROM NOTES. SEE |
| | SECTION 604.9 WATER HAMMER ARRESTORS ARE |
| | REQUIRED AT THE WASH MACHINE, ICE MAKER, |
| | AND DISHWASHER. |
| | |