Plan Review Notes
Plan Review Notes For Permit 04081247
Permit Number 04081247
Review Stop P
Sequence Number 1
Notes
Date Text
2004-10-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) BOTH SETS OF PLANS SHALL BE SIGNED,
 SEALED AND DATED BY THE ARCHITECT OF
 RECORD, AND SEAL SHALL SHOW ALL INFORM-
 ATION REQUIRED BY FAC 61G1-16.001 AND
 FS 481.221.
 2) TITLE BLOCK ON ALL SHEETS SHALL HAVE
 THE MINIMUM INFORMATION. FIRM LICENSE
 NUMBER, & SPACE FOR PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT. FAC 61G1-16
 .004(2) & (6). FS 481.2055
 3) A CERTIFICATE OF AUTHROIZATION NUMBER
 IS REQUIRED FOR THE ARCHITECTURAL COMP-
 ANY PER FS481.219
 4) SHT A-2 DEMO SHEET, IN THE INSTALLAT-
 ION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5. - ALL CAPPED PIPING SHALL
 BE INSPECTED PRIOR TO COVERING.
 5) SHT A-6 DETAIL 6 MASTER BATH SHOWER
 SHOWS 28" WIDTH. SECTION 417.4 STATES,
 SHOWER COMPARTMENTS SHALL NOT BE LESS
 THAN 30" IN MINIMUM DIMENSION MEASURED
 FROM THE FINISHED INTERIOR DIMENSION AND
 SHALL BE MEASURED AS THE SIDE OF A REC-
 TANGLE.
 6) SHT M-1 PLUMBING NOTES 9 AIR CHAMBERS
 ARE NOT APPROVED. DELETE FROM NOTES. SEE
 SECTION 604.9 WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASH MACHINE, ICE MAKER,
 AND DISHWASHER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]