| Date |
Text |
| 2004-08-31 00:00:00 | ************* UNSAT *************** |
| | |
| | **PLEASE SEE PLANS ARE NOT COMPLETE AT |
| | THIS TIME FOR COMPLETE REVIEW. |
| | PLEASE SEE THE FOLLOWING NOTES. |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR |
| | MISSING INFORMATION REQUIRED ON TITLE |
| | BLOCK. PLEASE ALSO SEE FS 481.219 FOR |
| | REQUIRED LICENSE #(S). |
| | PLEASE ALSO SEE ONLY ONE SET HAS BEEN |
| | SIOGNED AND SEALED. FBC 104.2.1 REQUIRES |
| | BOTH. |
| | |
| | 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 3 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 210.12 2002 NEC |
| | |
| | 4)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH A PANEL SCHED- |
| | -ULE TO BE SUBMITTED. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SEE PLANS SHOW A NEW |
| | 100A PANEL, YET NO OTHER INFORMATION IS |
| | GIVEN?? |
| | OCP, AWG, CONDUIT(S) ETC. |
| | PLEASE ALSO SUBMIT LOAD CALCAULTIONS |
| | PER 215.5,220.31B |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |