2004-10-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE PROPOSED CONNECTION OF ADJACENT
 CONDOS BREACHES THE FIRE SEPARATION
 BETWEEN UNITS.A 'UNITY OF TITLE' SHALL
 BE RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC 704.3
 TENANT SEPARATION REQUIREMENTS MAY BE
 DEEMED NOT APPLICABLE.
  
 2) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM LICENSE NUMBER (SEE
 COMMENT BELOW, RE: CERTIFICATE OF
 AUTHORIZATION)
 - INCLUDE THE PRINTED NAME AND LICENSE
 NUMBER OF THE ARCHITECT SEALING THE
 PLANS
 - HAVE THE SEAL DATED BY THE ARCHITECT
  
 3) 481.219(2) F.S.A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, PARTNERSHIP, OR PERSON
 PRACTICING UNDER A FICTITIOUS NAME,
 OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
  
 4) FBC 11-11THE BATHROOM DOOR AND THE
 DOORS LEADING TO THE BATHROOM SHALL HAVE
 A 29" CLEAR OPENING.
  
 5) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS