| Plan Review Notes For Permit 04081242 |
| Permit Number |
04081242 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-10-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | COMMENTS FROM PREVIOUS REVIEW HAVE NOT | | | BEEN ADDRESSED. | | | 1) ALL SHEETS, THE DATE PLANS ARE SIGNED | | | & SEALED IS REQUIRED ON THE SEAL. FAC | | | 61G1-16.003 - FS 481.2055 | | | 2) SHT 1 GENERAL NOTES: #1 ADOPTED CODE | | | IS FLORIDA BUILDING CODE-2001, NOT CABO. | | | CHANGE CODE REFERENCE. SECTION 104.2.1. | | | 3) SHT 3 SHOWER SHALL BE A MINIMUM OF | | | 30" WIDE FOR A FINISHED MEASURMENT. HAND | | | WRITTEN MEASURMENTS ARE NOT ACCEPTABLE. | | | SHOW MEASUREMENT ON NEW SHEET. SECTION | | | 417.4 (BATH #2) | | | 4) SHT 3, BATH #2 TOILET REQUIRES A 30" | | | OPENING MINIMUM. SECTION 405.3.1 - HAND | | | WRITTEN MEASURMENTS ARE NOT ACCEPTABLE. | | | 5) SHT 3 SHOW LENGTH AND WIDTH OF SHOWER | | | IN BATH #1. MINIMUM 900 SQ.IN. REQUIRED | | | PER SECTION 417.4. - HAND WRITTEN MEAS- | | | URMENTS NOT ACCEPTABLE. | | | 6) PROVIDE A WATER RISER DIAGRAM. SECT- | | | ION 104.3.1 | | | ****NEW COMMENTS | | | 1B) VENT REQUIRED FOR WASH MACHINE. SEC- | | | TION 902.1 | | | 2B) SEE ATTACHED SHEET CONCERNING FS | | | 553.80(2)(B). DESIGN PROFESSIONAL DOCU- | | | MENTS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|