Plan Review Notes
Plan Review Notes For Permit 04081242
Permit Number 04081242
Review Stop P
Sequence Number 1
Notes
Date Text
2004-09-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ALL SHEETS, THE DATE PLANS ARE SIGNED
 & SEALED IS REQUIRED ON THE SEAL. FAC
 61G1-16.003 - FIRM LICENSE NUMBER IS RE-
 QUIRED ON THE TITLE BLOCK. FAC 61G1-16.
 004(2) - PRINTED NAME OF PERSON THAT
 SEALS THE PLAN REQUIRED ON THE TITLE
 BLOCK, FAC 61G1-004(6) - CERTIFICATE OF
 AUTHROIZATION IS REQUIRED ON THE TITLE
 BLOCK, FS 481.219.- FS 481.2055
 2) SHT 1 GENERAL NOTES: #1 ADOPTED CODE
 IS FLORIDA BUILDING CODE - 2001, NOT
 CABO. CHANGE CODE REFERENCE. SECTION
 104.2.1
 3) SHT 3 SHOWER SHALL BE A MINIMUM OF
 30" WIDE FOR A FINISHED MEASUREMENT, AND
 REQUIRES A 2" TRAP MINIMUM. SECTION
 417.4 AND TABLE 709.1. BATH #2
 4) SHT 3 BATH #2 TOILET REQUIRES A 30"
 OPENING MINIMUM.
 5) SHT 3 SHOW LENGTH AND WIDTH OF SHOWER
 IN BATH #1. MINIMUM 900 SQ.IN. REQUIRED
 PER SECTION 417.4
 6) PROVIDE A SANITARY RISER DIAGRAM AND
 A WATER RISER DIAGRAM IN ISOMETRIC FORM
 FOR ALL NEW WORK. SECTION 104.3.1.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]