| 2004-08-31 00:00:00 | ********** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE SHEETS SIGNED AND |
| | SEALED BY ARCH IS REQUIRED TO HAVE A |
| | TITLE BLOCK PER FAC 61G1-16.004 |
| | PLEASE SEE ABOVE FOR ALL INFORMATION |
| | REQUIRED ON TITLE BLOCK. |
| | PLEASE ALSO SEE FS 481.219 FOR REQUIRED |
| | LICENSE #(S). |
| | THIS IS REQUIRED ON ALL SHEETS WHEATHER |
| | OR NOT COMMENT IS MADE BY OTHER REVIEW- |
| | -ERS. |
| | |
| | 2 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | PLEASE INDICATE FOR ANY NEW BRANCH CIR- |
| | -CUITS TO SLEEPING RMS.2002 NEC 210.12 |
| | |
| | 3)NOTE: PLEASE SHOW CIRCUITING ON PLANS |
| | AND CORRELATE WITH A PANEL SCHEDULE. |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2 |
| | AND 8-1.4.2 FOR SD'S REQUIRED AND IF |
| | W/IN 20' OF COOKING APPLIANCE. |
| | |
| | 5) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THEY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |