Plan Review Notes
Plan Review Notes For Permit 04081185
Permit Number 04081185
Review Stop E
Sequence Number 2
Notes
Date Text
2005-05-03 00:00:00******** UNSAT *********
  
 PLEASE SEE REVISIONS APPEAR TO BE FOR
 FINALS. PLEASE SEE BELOW COMMENTS AND
 REDLINED PLANS.
  
 1)NOTE: PLEASE CORRELATE FEEDERS FOR
 POOL SUB PANEL. PLEASE SEE PANEL "B"
 WHICH SHOWS 3-#6'S AND SEE RISER.
 PLEASE SEE #OF #6'S SHOWN FOR AHU'S ,
 SEE KW , OCP AND AWG FOR COND UNITS.
  
 PLEASE ADJUST PER ACTUAL INSTALLATION.
  
 2)NOTE: PLEASE SEE 6KW LOAD SHOWN FOR
 COOKTOP ON 20A CIRCUIT AND #12. THIS
 APPEARS TO BE A GAS COOKTOP.
  
 3)NOTE: PLEASE SEE DRYER SHOWN @5KW ON
 20A CIRCUIT. PLEASE SEE PLANS INDICATE A
 GAS DRYER??
 PLEASE SEE 240.4,310.16
  
 4)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
  
 PLEASE SEE ONE SET OF PLANS HAVE BEEN
 REDLINED FOR AREAS NOTED. IF THERE ARE
 ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]