| Plan Review Notes For Permit 04081185 |
| Permit Number |
04081185 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-05-03 00:00:00 | ******** UNSAT ********* | | | | | | PLEASE SEE REVISIONS APPEAR TO BE FOR | | | FINALS. PLEASE SEE BELOW COMMENTS AND | | | REDLINED PLANS. | | | | | | 1)NOTE: PLEASE CORRELATE FEEDERS FOR | | | POOL SUB PANEL. PLEASE SEE PANEL "B" | | | WHICH SHOWS 3-#6'S AND SEE RISER. | | | PLEASE SEE #OF #6'S SHOWN FOR AHU'S , | | | SEE KW , OCP AND AWG FOR COND UNITS. | | | | | | PLEASE ADJUST PER ACTUAL INSTALLATION. | | | | | | 2)NOTE: PLEASE SEE 6KW LOAD SHOWN FOR | | | COOKTOP ON 20A CIRCUIT AND #12. THIS | | | APPEARS TO BE A GAS COOKTOP. | | | | | | 3)NOTE: PLEASE SEE DRYER SHOWN @5KW ON | | | 20A CIRCUIT. PLEASE SEE PLANS INDICATE A | | | GAS DRYER?? | | | PLEASE SEE 240.4,310.16 | | | | | | 4)NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | | | | | | | PLEASE SEE ONE SET OF PLANS HAVE BEEN | | | REDLINED FOR AREAS NOTED. IF THERE ARE | | | ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|