| 2004-09-15 00:00:00 | ******** UNSAT ******* |
| | |
| | 1)NOTE: PLEASE SEE TITLE BLOCK FOR ENGI- |
| | -NEER REQUIRED TO HAVE PRINTED LICENSE |
| | #. 61G15-23.002 |
| | PLEASE ALSO SEE FS 471.023, A LEGAL |
| | SIGNATURE IS REQUIRED. APPEARS TO BE |
| | INITIALS?? |
| | |
| | 2)NOTE: PLEASE SEE TITLE BLOCK FOR |
| | DESIGN AND ASSC'S. FS 481.219, 61G1-16.- |
| | -.004. PLEASE INCLUDE ALL LICENSE INFOR- |
| | -MATION. |
| | |
| | 3)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2 |
| | |
| | 4)NOTE: PLEASE CORRRLELATE SIZE OF HEAT/ |
| | KW WITH MECHANICAL SPECS. PLEASE ALSO |
| | SEE 424.3B FOR REQUIRED MIN OCP OF 125%. |
| | |
| | 5 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC 210.12 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |