| Plan Review Notes For Permit 04081124 |
| Permit Number |
04081124 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT 3 SANITARY RISER DIAGRAM DOES NOT | | | MEET THE CODE REQUIREMENTS. | | | A) LAV IS NOT VENTED, AND PIPED AS | | | SHOWN WILL BE AN "S" TRAP WHICH IS NOT | | | APPROVED. SECTION 1002.3(5) | | | B) ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUP SHALL CONNECT TO THE | | | WET-VENTED HORIZONTAL BRANCH DRAIN. ANY | | | ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. SECTION | | | 909.1 (THE WASH MACHINE SHALL CONNECT | | | DOWNSTREAM OF THE BATHROOM FIXTURES). | | | 2) SEE RED-LINE CORRECTIONS ON ONE SET | | | OF PLANS SHOWING HOW THIS CAN BE | | | CORRECTED. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|