| 2004-11-24 00:00:00 | **** UNSAT **** |
| | |
| | |
| | 1)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | |
| | 2)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | ** PLEASE SEEMISSING INSIDE AND |
| | OUTSIDE NEW BEDRM. |
| | |
| | 3)NOTE: PLEASE SEE 210.52C3/ 210.8A6 FOR |
| | MISSING GFI RECEPT FOR NEW PENINSULAR. |
| | |
| | 4)NOTE: PLEASE SEE MISSING RECEPT FOR 2' |
| | OF WALL IN NEW MASTER BEDRM. 210.52 |
| | |
| | 5)NOTE: PLEASE SEE RECEPT OUTSIDE TO BE |
| | GFI. 210.8 |
| | |
| | 6)NOTE: PLEASE VERIFY PANEL LOCATION AND |
| | LOCATION OF WHAT IS TO BE A J-BOX IN NEW |
| | BATHRM WALL. |
| | |
| | 7)NOTE: PLEASE SEE 1P60A POOL-PUMP?? |
| | PLEASE VERIFY. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY AFFET ELECTRICAL |
| | SHEETS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |