Plan Review Notes
Plan Review Notes For Permit 04081124
Permit Number 04081124
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-24 00:00:00**** UNSAT ****
  
  
 1)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
  
 2)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 ** PLEASE SEEMISSING INSIDE AND
 OUTSIDE NEW BEDRM.
  
 3)NOTE: PLEASE SEE 210.52C3/ 210.8A6 FOR
 MISSING GFI RECEPT FOR NEW PENINSULAR.
  
 4)NOTE: PLEASE SEE MISSING RECEPT FOR 2'
 OF WALL IN NEW MASTER BEDRM. 210.52
  
 5)NOTE: PLEASE SEE RECEPT OUTSIDE TO BE
 GFI. 210.8
  
 6)NOTE: PLEASE VERIFY PANEL LOCATION AND
 LOCATION OF WHAT IS TO BE A J-BOX IN NEW
 BATHRM WALL.
  
 7)NOTE: PLEASE SEE 1P60A POOL-PUMP??
 PLEASE VERIFY.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFET ELECTRICAL
 SHEETS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]