| Plan Review Notes For Permit 04081123 |
| Permit Number |
04081123 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-01-04 00:00:00 | PLAN DENIED | | | 1) CAN NOT INSTALL OUTDOOR AIR ON ROOF | | | SECTION 609.1.ABC.1#2 FLORIDA ENERGY | | | CODE. | | | 2) REFER TO SECTION 601.4 FBC(M)BALANCED | | | RERURN AIR SIZEING | | | 3) PLANS MUST BE STAMPED OR TITLE BLOCK | | | CUT OFF. | | | 4) DO NOT NEED RETURN AIR IN BATHROOM OR | | | CLOSET. | | | 5) REFER TO SECTION 307.2.3 AUXILIARY | | | DRAIN FBC.(M) | | | 6) REFER TO SECTION 1107.2.1 REFRIGERANT | | | PIPING | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 | | | | | | | | | |
|