| 2004-08-30 00:00:00 | ********* UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G1-16.004 |
| | PLEASE ALSO INCLUDE PRINTED NAME AND |
| | LICENSE # FOR ARCH OF RECORD IN TITLE |
| | BLOCK. |
| | THIS IS REQUIRED ON ALL SHEETS. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | ** MISSING SD LEADING TO FLR ABOVE. ** |
| | |
| | 4)NOTE: PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63 |
| | PLEASE ALSO SHOW LOCATIONS FOR CU'S AND |
| | PLEASE SEE 440.11 FOR DISC MEANS. |
| | |
| | 5)NOTE: PLEASE SEE 220.31B FOR LOAD |
| | CALCULATIONS. |
| | PLEASE ADJUST. |
| | |
| | 6)NOTE: PLEASE SEE 424.3B FOR OCP ON |
| | HEAT OF AHU'S. |
| | |
| | 7)NOTE: PLEASE SEE 250.6,250.24, NO |
| | EQUIPMENT GROUNDING TO BE INSTALLED |
| | UNTIL AFTER THE FIRST MEANS OF DISC. |
| | |
| | 8)NOTE: PLEASE SEE MISSING RECEPT ON 2' |
| | OF WALL IN MAST BR. 210.52 |
| | |
| | 9 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 210.12 2002 NEC |
| | |
| | 10)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 11)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| | ADDTIONS TO EXSITING DWELLINGS. |
| | PLEASE PROVIDE LAYOUT OF EXSIT. THIS IS |
| | TO BROUGHT UP TO CODE OR IF EXISTING |
| | MEETS 2002 NEC |
| | PLEASE ALSO SEE SD'S TO MEET NFPA-72 |
| | PER PREVIOUS NOTE. |
| | |
| | 12)NOTE: PLEASE SEE KVA SHOWN FOR A/C |
| | AHU'S DO NOT APPEAR TO CORRELATE TO |
| | LOAD CALCS? |
| | |
| | 13)NOTE: PLEASE ALSO SEE BLDG REVIEW |
| | NOTES FOR VALUATION OF PERMIT. |
| | SHOWN AT 45K FOR 3240 SQ FT. |
| | VALUE TO BE ADJUSTED. PER FBC 104.6.5. |
| | |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD PLANS |
| | FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |