Plan Review Notes
Plan Review Notes For Permit 04081123
Permit Number 04081123
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-30 00:00:00********* UNSAT ******************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004
 PLEASE ALSO INCLUDE PRINTED NAME AND
 LICENSE # FOR ARCH OF RECORD IN TITLE
 BLOCK.
 THIS IS REQUIRED ON ALL SHEETS.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 ** MISSING SD LEADING TO FLR ABOVE. **
  
 4)NOTE: PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
 PLEASE ALSO SHOW LOCATIONS FOR CU'S AND
 PLEASE SEE 440.11 FOR DISC MEANS.
  
 5)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS.
 PLEASE ADJUST.
  
 6)NOTE: PLEASE SEE 424.3B FOR OCP ON
 HEAT OF AHU'S.
  
 7)NOTE: PLEASE SEE 250.6,250.24, NO
 EQUIPMENT GROUNDING TO BE INSTALLED
 UNTIL AFTER THE FIRST MEANS OF DISC.
  
 8)NOTE: PLEASE SEE MISSING RECEPT ON 2'
 OF WALL IN MAST BR. 210.52
  
 9 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12 2002 NEC
  
 10)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 11)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDTIONS TO EXSITING DWELLINGS.
 PLEASE PROVIDE LAYOUT OF EXSIT. THIS IS
 TO BROUGHT UP TO CODE OR IF EXISTING
 MEETS 2002 NEC
 PLEASE ALSO SEE SD'S TO MEET NFPA-72
 PER PREVIOUS NOTE.
  
 12)NOTE: PLEASE SEE KVA SHOWN FOR A/C
 AHU'S DO NOT APPEAR TO CORRELATE TO
 LOAD CALCS?
  
 13)NOTE: PLEASE ALSO SEE BLDG REVIEW
 NOTES FOR VALUATION OF PERMIT.
 SHOWN AT 45K FOR 3240 SQ FT.
 VALUE TO BE ADJUSTED. PER FBC 104.6.5.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD PLANS
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]